๐ฏ The 9388B cuts 8 loads before the 15-minute average can reach 18. That is the right tool. Three holes still let the meter print a 20.8. Close them and the guarantee is real.
| Load it cannot shed | kW, worst case |
|---|---|
| LED video wall (49 cabinets) | 6 to 9 |
| Live Room light rig | 2 to 4 |
| Kitchen + fridges | 1.5 to 3 |
| Console, gear, 4 rooms | 2.5 to 5 |
| Tesla at the 12 A cap | 2.8 |
| Everything at once | 15 to 24 |
| Step | Now says | Should say |
|---|---|---|
| 3 Brayden quote | 8 loads, 7 AC + sauna | 9 loads: Tesla contactor + sauna + 7 AC, relay expansion, alarm |
| 4 Eyedro | order it this week | order it this week and install it now: 2 weeks of floor data before the C-10 visit |
| 5 C-10 scope | panel, 7 pilot relays, sauna contactor | add 60 A Tesla contactor + meter-to-load map for all 9 |
| 6 Shed order | sauna first, then ACs | Tesla, sauna, (LED wall if the floor says so), then ACs |
| 7 Install day | shed one AC and watch | also start a 48 A charge and watch it get cut |
| Greg | files after two clean weeks | first pulls Green Button for Jul 28 |
taji.html was not changed by this audit. The six edits above are ready to apply on your word.